Phone
MON - FRI
09:00 - 18:00
01865987497

Quadruple System Ceiling Ducted - Mr Slim PEAD-RP Standard Inverter Heat Pump (Three Phase)

  • From £4,388.00


Available Options


Quadruple System Ceiling Ducted - Mr Slim PEAD-RP Standard Inverter Heat Pump (Three Phase)

Our Standard Inverter range offers customers all the features and benefits of inverter technology whilst being cost effective.

Key Features

  • Reduced height - entire range only 250mm
  • Wider range of external static pressure settings across entire range
  • Drain pump included as standard
INDOOR UNITS PEAD- RP50JAQ RP60JAQ
CAPACITY (kW) Heating (nominal) 5.9 (1.7-7.2) 7.0 (2.5-8.0)
Cooling (nominal) 4.9 (2.3-5.6) 5.7 (2.3-6.3)
Heating (UK) 5.02 (1.45-6.12) 5.95 (2.13-6.80)
Cooling (UK) 4.51 (2.12-5.15) 5.24 (2.12-5.80)
SHF (nominal & UK)   0.85 0.86
COP / EER (nominal)   3.64 / 3.31 3.63 / 3.41
SCOP / SEER (BSEN14825)   4.2 / 5.4 4.0 / 5.6
ENERGY EFFICIENCY CLASS Heating / Cooling A+ / A A+ / A+
AIRFLOW (l/s) Lo-Mi1-Mi2-Hi 200-242-283 242-300-350
PIPE SIZE mm (in) Gas 12.7 (1/2”) 15.88 (5/8”)
Liquid 6.35 (1/4”) 6.35 (1/4”)
EXTERNAL STATIC PRESSURE (Pa)   35-50-70-100-150 35-50-70-100-150
SOUND PRESSURE LEVEL (dBA) Lo-Mi-Hi 26-31-35 25-29-33
SOUND POWER LEVEL (dBA)   57 55
DIMENSIONS (mm) W x D x H (Grille) 900 x 732 x 250 1100 x 732 x 250
WEIGHT (kg) Unit / Panel 28 33
ELECTRICAL SUPPLY   Fed by Outdoor Unit Fed by Outdoor Unit
FUSE RATING (BS88) – HRC (A)   6 6
INTERCONNECTING CABLE No. Cores   4 4
OUTDOOR UNITS PUHZ- P200YKA2 P250YKA2
SOUND PRESSURE LEVEL (dBA) Heating / Cooling 60 / 58 62 / 59
WEIGHT (kg)   127 135
DIMENSIONS (mm) W x D x H 1050 x 330+40 x 1338 1050 x 330+40 x 1338
ELECTRICAL SUPPLY   380-415v, 50Hz 380-415v, 50Hz
PHASE   Three Three
SYSTEM POWER Heating / Cooling (nominal) 7.36 / 7.21 8.47 / 8.44
INPUT (kW) Heating / Cooling (UK) 6.18 / 6.13 7.12 / 7.17
STARTING CURRENT (A)   5 5
SYSTEM RUNNING CURRENT (A) Heating / Cooling [MAX] 9.88 / 9.47 [19] 12.0 / 11.0 [21]
FUSE RATING (BS88) – HRC (A)   20 25
MAINS CABLE No. Cores   5 5
MAX PIPE LENGHT (m)   70 70
MAX HEIGHT DIFFERENCE (m)   30 30
CHARGE R410A (kg)   5.8 7.1

Notes: price includes separate PAR-32MAA wired remote controller.