Phone
MON - FRI
09:00 - 18:00
07827594499

Mitsubishi Electric PEAD-RP Standard Inverter Heat Pump (Single Phase)

  • From £1,004.00


Available Options


Mitsubishi Electric PEAD-RP Standard Inverter Heat Pump (Single Phase)

Our Standard Inverter range offers customers all the features and benefits of inverter technology whilst being cost effective.

Key Features

  • Reduced height - entire range only 250mm
  • Wider range of external static pressure settings across entire range
  • Drain pump included as standard
INDOOR UNITS PEAD- RP35JAQ RP50JAQ RP60JAQ RP71JAQ RP100JAQ RP125JAQ RP140JAQ
CAPACITY (kW) Heating (nominal) 4.1 (1.7-5.0) 5.9 (1.7-7.2) 7.0 (2.5-8.0) 8.0 (2.6-10.2) 11.2 (4.5-12.5) 14.0 (5.0-16.0) 16.0 (5.0-18.0)
Cooling (nominal) 3.6 (1.4-3.9) 4.9 (2.3-5.6) 5.7 (2.3-6.3) 7.1 (2.8-8.1) 9.4 (4.9-11.2) 12.3 (5.5-14.0) 13.6 (5.5-15.0)
Heating (UK) 3.49 (1.45-4.25) 5.02 (1.45-6.12) 5.95 (2.13-6.80) 6.80 (2.21-8.67) 9.5 (3.85-10.65) 11.9 (4.25-13.6) 13.6 (4.25-15.3)
Cooling (UK) 3.31 (1.29-3.59) 4.51 (2.12-5.15) 5.24 (2.12-5.80) 6.53 (2.58-7.45) 8.65 (4.5-10.3) 11.3 (5.05-12.9) 12.5 (5.05-13.8)
SHF (nominal & UK)   0.85 0.85 0.86 0.83 0.85 0.85 0.84
COP / EER (nominal)   3.69 / 3.42 3.64 / 3.31 3.63 / 3.41 3.92 / 3.41 3.61 / 3.01 3.62 / 2.91 3.61 / 3.01
SCOP / SEER (BSEN14825)   4.0 / 5.5 4.2 / 5.4 4.0 / 5.6 3.9 / 5.8 3.8 / 4.6 3.9 / 3.5 3.7 / 3.2
ErP ENERgY EFFICIENCY CLASS Heating / Cooling A+ / A A+ / A A+ / A+ A / A+ A / B N/A N/A
AIRFLOW (l/s) Lo-Mi-Hi 167-200-233 200-242-283 242-300-350 292-350-417 400-483-567 492-558-700 533-650-767
PIPE SIZE mm (in) Gas 9.52 (3/8”) 12.7 (1/2”) 15.88 (5/8”) 15.88 (5/8”) 15.88 (5/8”) 15.88 (5/8”) 15.88 (5/8”)
Liquid 6.35 (1/4”) 6.35 (1/4”) 6.35 (1/4”) 9.52 (3/8”) 9.52 (3/8”) 9.52 (3/8”) 9.52 (3/8”)
EXTERNAL STATIC PRESSURE (Pa)   35-50-70-100-150
SOUND PRESSURE LEVEL (dBA) Lo-Mi-Hi 23-27-30 26-31-35 25-29-33 26-30-34 29-34-38 33-36-40 34-38-43
SOUND POWER LEVEL (dBA)   52 57 55 58 61 66 66
DIMENSIONS (mm) W x D x H 900 x 732 x 250 900 x 732 x 250 1100 x 732 x 250 1100 x 732 x 250 1400 x 732 x 250 1400 x 732 x 250 1600 x 732 x 250
WEIGHT (kg) Unit / Panel 26 28 33 33 41 43 47
ELECTRICAL SUPPLY   Fed by Outdoor Unit
FUSE RATING (BS88) – HRC (A)   6 6 6 6 6 6 6
INTERCONNECTING CABLE No. Cores   4 4 4 4 4 4 4
OUTDOOR UNITS SUZ- / PUHZ- KA35VA6 KA50VA6 KA60VA6 KA71VA6 P100VHA5 P125VHA4 P140VHA4
SOUND PRESSURE LEVEL (dBA) Heating / Cooling 50 / 49 52 / 52 55 / 55 55 / 55 54 / 50 55 / 51 56 / 52
SOUND POWER LEVEL (dBA) Cooling 62 65 65 69 70 71 73
WEIGHT (kg)   35 54 50 53 75 99 99
DIMENSIONS (mm) W x D x H 800 x 285 x 550 840 x 330 x 880 840 x 330 x 880 840 x 330 x 880 950 x 330 + 30 x 943 950 x 330 + 30 x 1350 950 x 330 + 30 x 1350
ELECTRICAL SUPPLY   220-240v, 50Hz
PHASE   Single Single Single Single Single Single Single
SYSTEM POWER INPUT (kW) Heating / Cooling (nominal) 1.11 / 1.05 1.62 / 1.48 1.93 / 1.67 2.04 / 2.08 3.10 / 3.12 3.87 / 4.22 4.43 / 4.52
Heating / Cooling (UK) 0.93 / 0.89 1.36 / 1.26 1.62 / 1.42 1.71 / 1.75 2.6 / 2.65 3.25 / 3.59 3.72 / 3.80
STARTING CURRENT (A)   5.1 7.3 8.4 9.3 12.0 15.0 15.0
SYSTEM RUNNING CURRENT (A) Heating / Cooling [MAX] 4.90 / 5.10 [9.3] 6.90 / 7.30 [13.4] 7.40 / 8.40 [15.6] 9.30 / 9.10 [18.1] 16.27 / 15.55 [30.65] 19.03 / 19.66 [30.76] 23.8 / 24.97 [32.28]
FUSE RATING (BS88) – HRC (A)   16 20 20 20 32 32 40
MAINS CABLE No. Cores   3 3 3 3 3 3 3
MAX PIPE LENGHT (m)   20 30 30 30 50 50 50
MAX HEIGHT DIFFERENCE (m)   12 30 30 30 30 30 30
CHARGE R410A (kg)   1.15 1.60 1.80 1.80 3.0 4.5 4.5

Notes: All units charged to 7m (35-71), 30m (100-140) pipe length. Indoor price includes separate PAR-32MAA wired remote controller.

Write a review

Note: HTML is not translated!
    Bad           Good

Tags: mr.slim, pead-rp, standard, inverter, heat, pump, (single, phase), ducted, models mitsubishi, electric