Twin System Ducted - Mr Slim PEAD-RP Standard Inverter Heat Pump (Single Phase)

  • From £2,065.00


Available Options


Twin System Ducted - Mr Slim PEAD-RP Standard Inverter Heat Pump (Single Phase)

Our Standard Inverter range offers customers all the features and benefits of inverter technology whilst being cost effective.

Key Features

  • Reduced height - entire range only 250mm
  • Wider range of external static pressure settings across entire range
  • Drain pump included as standard
INDOOR UNITS PEAD- RP50JAQ RP60JAQ RP71JAQ
CAPACITY (kW) Heating (nominal) 5.9 (1.7-7.2) 7.0 (2.5-8.0) 8.0 (2.6-10.2)
Cooling (nominal) 4.9 (2.3-5.6) 5.7 (2.3-6.3) 7.1 (2.8-8.1)
Heating (UK) 5.02 (1.45-6.12) 5.95 (2.13-6.80) 6.80 (2.21-8.67)
Cooling (UK) 4.51 (2.12-5.15) 5.24 (2.12-5.80) 6.53 (2.58-7.45)
SHF (nominal & UK)   0.85 0.86 0.83
COP / EER (nominal)   3.64 / 3.31 3.63 / 3.41 3.92 / 3.41
SCOP / SEER (BSEN14825)   4.2 / 5.4 4.0 / 5.6 3.9 / 5.8
ErP ENERgY EFFICIENCY CLASS Heating / Cooling A+ / A A+ / A+ A / A+
AIRFLOW (l/s) Lo-Mi-Hi 200-242-283 242-300-350 292-350-417
PIPE SIZE mm (in) Gas 12.7 (1/2”) 15.88 (5/8”) 15.88 (5/8”)
Liquid 6.35 (1/4”) 6.35 (1/4”) 9.52 (3/8”)
EXTERNAL STATIC PRESSURE (Pa)   35-50-70-100-150 35-50-70-100-150 35-50-70-100-150
SOUND PRESSURE LEVEL (dBA) Lo-Mi-Hi 26-31-35 25-29-33 26-30-34
SOUND POWER LEVEL (dBA)   57 55 58
DIMENSIONS (mm) W x D x H 900 x 732 x 250 1100 x 732 x 250 1100 x 732 x 250
WEIGHT (kg) Unit / Panel 28 33 33
ELECTRICAL SUPPLY   Fed by Outdoor Unit
FUSE RATING (BS88) – HRC (A)   6 6 6
INTERCONNECTING CABLE No. Cores   4 4 4
OUTDOOR UNITS PUHZ- P100VHA5 P125VHA4 P140VHA4
SOUND PRESSURE LEVEL (dBA) Heating / Cooling 54 / 50 55 / 51 56 / 52
SOUND POWER LEVEL (dBA) Cooling 70 71 73
WEIGHT (kg)   75 99 99
DIMENSIONS (mm) W x D x H 950 x 330 + 30 x 943 950 x 330 + 30 x 1350 950 x 330 + 30 x 1350
ELECTRICAL SUPPLY   220-240V, 50Hz
PHASE   Single Single Single
SYSTEM POWER INPUT (kW) Heating / Cooling (nominal) 3.10 / 3.12 3.87 / 4.22 4.43 / 4.52
Heating / Cooling (UK) 2.6 / 2.65 3.25 / 3.59 3.72 / 3.80
STARTING CURRENT (A)   12.0 15.0 15.0
SYSTEM RUNNING CURRENT (A) Heating / Cooling [MAX] 16.27 / 15.55 [30.65] 19.03 / 19.66 [30.76] 23.8 / 24.97 [32.28]
FUSE RATING (BS88) – HRC (A)   32 32 40
MAINS CABLE No. Cores   3 3 3
MAX PIPE LENGHT (m)   50 50 50
MAX HEIGHT DIFFERENCE (m)   30 30 30
CHARGE R410A (kg)   3.0 4.5 4.5

Note: All units charged to 7m (35-71), 20m (100) and 30m (125-140) pipe length. Indoor price includes seperate PAR-32MAA wired remote controller.