Phone
MON - FRI
09:00 - 18:00
07827594499

Built in DC Ducted - Seasonal Classic Inverter FBQ / RZQSG (Single Phase)

  • Brand: Daikin
  • Product Code: FBQ71C8 / RZQSG71L3V1
  • Availability: In Stock
  • From £1,799.00


Available Options


Built in DC Ducted - Seasonal Classic Inverter FBQ / RZQSG (Single Phase)

Features:

  • The new inverter fan ducted units, provides both drastic energy savings and simplifies installation
  • Automatically adjusts air volume against ESP at commissioning
  • Seasonally Efficient Inverter Technology gives up to 25% better efficiency than inverter technology
  • Comms, computer and server room cooling possible with EDP setting
  • Selectable evaporating & condensing temperature for greater operating efficiency
  • Fan speed: 2 fan speeds can be selected, high or low
  • Suitable for Twin, Triple and Double Twin applications
  • Re-use of existing R22 and R407C piping possible
  • DIII net compatibility as standard
INDOOR UNITS   FBQ71C8 FBQ100C8 FBQ125C8 FBQ140C8
Cooling Capacity kW 6.80 9.50 12.00 13.40
Heating Capacity kW 7.50 10.80 13.50 15.50
Seasonal Eiciency (EN14825) COOLING Energy Label A+ A A -
Pdesign kW 6.80 9.50 12.00 -
SEER 5.81 5.50 5.20 -
Annual Energy Consumption kWh 410 604 807 -
Seasonal Eiciency (EN14825) HEATING Energy Label A A+ A -
Pdesign kW 6.00 7.60 7.60 -
SEER 3.88 4.01 3.90 -
Annual Energy Consumption kWh 2166 2653 2728 -
Nominal Efficiency EER / COP 3.28 / 3.61 3.31 / 3.65 3.21 / 3.51 3.02 / 3.41
Energy Label A / A A / A A / B B / B
Annual Energy Consumption kWh 1037 1435 1870 2220
Air Flow Rate High / Low m3/min 18 / 15 32 / 23 39 / 28 39 / 28
Dimensions Height mm 300 300 300 300
Width mm 1000 1400 1400 1400
Depth mm 700 700 700 700
Weight kg 34 45 45 45
Sound Pressure High / Low dBA 37 / 29 38 / 32 40 / 33 41 / 34
Sound Power dBA 57 61 66 66
OUTDOOR UNITS   RZQSG71L3V1 RZQSG100L8V1 RZQSG125L8V1 RZQSG140LV1
Dimensions Height x Width x Depth mm 770 x 900 x 320 990 x 940 x 320 990 x 940 x 320 1430 x 940 x 320
Weight kg 67 81 81 102
Min. ambient operating temperatures Cooling / Heating °C -15 / -15
Electrical Details Power Supply 1ph
Running Current A 8.46 11.73 15.29 18.15
Starting Current A 4 4 4 4
Max Fuse Size A 20 32 32 32
Interconnection Wiring Core / Cable size 3+E / 1.5
Piping Connections Liquid / Gas inches 3/8 / 5/8 3/8 / 5/8 3/8 / 5/8 3/8 / 5/8
Pipework Maximum Length m 50 50 50 50
Maximum Vertical Rise m 30 30 30 30
Precharged to m 30 30 30 30
Additional Charge g/m Refer to Installation Manual
Holding Charge kg 2.75 2.9 2.9 4.0
Sound Pressure High dBA 49 53 54 53
Sound Power dBA 65 69 70 69

Notes:

  • All fan coils supplied as standard with BRC1E52A wired remote controller with 7-day time clock
  • All fan coil units standard with auto restart after power failure
  • All fan coils supplied as standard with air filter

Write a review

Note: HTML is not translated!
    Bad           Good

Tags: built, ducted, seasonal, classic, inverter, fbq, rzqsg, (single, phase), models